Systemicon Abgassysteme einwandig
Oil
Gas
Solid fueles
Negative pressure 40Pa
Wet operating mode
Temperature up to 600°
Wall thickness 0,6 mm
Discount group EW
25 years warranty

EW-FU

Single-wall exhaust system made of stainless steel

Our renovation classic EW-FU is a single-wall system flue gas installation made of high-quality, moisture-resistant V4A stainless steel. It is the top choice for modernizing and reducing the cross-section of existing classic chimneys or for creating a connecting line from the boiler to the chimney. The system is suitable for all fuels with flue gas temperatures of up to 600°C in negative pressure operation. Thanks to a simple socket-bead connection, the individual chimney components can be quickly assembled.
 

SYSTEM_DETAIL_ICONS


Product Description

Features

  • Soot fire resistant or moisture resistant
  • Quick assembly and uncomplicated angled guidance due to lightweight material
  • Optional fixation with clamping bands
  • Available optionally as an oval pipe, ideal for tight and multi-flue systems
  • Wide variety of systems and extensive range of accessories

Applications

  • Standard heating appliances for oil, gas, solid fuels
    (natural wood, coke, peat, coal*)

* excluding anthracite coal from Ibbenbüren

Technical Data

Material1.4404 (316L) / 1.4571 (316Ti)
1.4828 available for an additional charge
Others on request
SurfaceMatte
Wall Thickness0,6 mm
Others on request
Inner Diameter80 - 600 mm
Others on request
InsulationOptional available with insulation jackets
ConnectionSocket / bead connection
EW-FU

CE CERTIFICATE NUMBER

0036 CPR 9174 006

CE CLASSIFICATIONS ACCORDING TO DIN EN 1856 - 1

T400 - N1 - D - V2 - L50060 - Gxx
T400 - N1 - W - V2 - L50060 - Oxx
T600 - N1 - D - V2 - L50060 - Gxx
T600 - N1 - W - V2 - L50060 - Oxx
T600 - N1 - D - V3 - L50060 - Gxx1

1 with 25 mm insulation
xx = Distances to combustible materials are
diameter-dependent, see declaration of performance

 

EW - FU CONNECTION PIPE

CE CERTIFICATE NUMBER

0036 CPR 9174 026

CE CLASSIFICATIONS ACCORDING TO DIN EN 1856-2

Without radiation protection:
T400 - N1 - D - V2 - L50060 - G400M
T400 - N1 - W - V2 - L50060 - O400M
T600 - N1 - D - V2 - L50060 - G400M

With radiation protection:
T400 - N1 - D - V2 - L50060 - G300
T400 - N1 - W - V2 - L50060 - O300
T600 - N1 - D - V2 - L50060 - G300

Contact